Shandong Science ›› 2022, Vol. 35 ›› Issue (3): 54-61.doi: 10.3976/j.issn.1002-4026.2022.03.007
• Energy and Power • Previous Articles Next Articles
ZHAO Xue-shan(),PAN Xiao-jun*
Received:
Online:
Published:
Contact:
Abstract:
To improve the throttling loss of an electric water feed pump during the deep peak shaving operation of northeast coal-fired units, and the utilization rate of electric energy and coal consumption, a 600 MW electric water feed pump unit in power plant is taken as an example, using a frequency conversion scheme, under different working conditions (100%, 92%, 83%, 67%, 60%, 53%, and 50% rated loads), to analyze the power and frequency conversion conditions of single and double water feed pumps and identify the relationship between the flow rate, load, electrical efficiency, and active power of the motor. The test results show that the lower the flow, the more greater will be the improvements in the electrical efficiency and active power of the motor, up to 30% and 33%, respectively, subsequent to frequency conversion. Frequency conversion transformation is suitable for this unit, reducing the plant power consumption rate by 0.45%~0.87%, the power saving rate is 21%~33%. The variable frequency drive has a significant energy-saving effect on the deep peak shaving operation of the unit, providing a certain degree of reference for the transformation of the same type of unit.
Key words: :deep peak shaving, power plant boiler water feed pump, frequency conversion transformation, power saving, energy saving
CLC Number:
ZHAO Xue-shan,PAN Xiao-jun. Energy-saving analysis of the frequency conversion transformation of an electric boiler water feed pump of the deep peak regulation unit[J].Shandong Science, 2022, 35(3): 54-61.
0 / / Recommend
Add to citation manager EndNote|Reference Manager|ProCite|BibTeX|RefWorks
URL: https://www.sdkx.net/EN/10.3976/j.issn.1002-4026.2022.03.007
https://www.sdkx.net/EN/Y2022/V35/I3/54
Fig.1
Flow chart of water-supply system"
Fig.2
24-pulse phase shift transformer"
Fig.3
Structure diagram of adding frequency conversion to water-supply pump group"
Table 1
Performance test parameters of water feed pump set(AB double pump operation)"
Table 2
Main calculation results of the performance test of the water feed pump group(AB double pump operation)"
Table 3
Performance test parameters of water feed pump set(A single pump operation)"
Table 4
Main calculation results of the performance test of the water feed pump group(A single pump operation)"
Fig.4
Relationship curve between the flow rate and efficiency of the water feed pump set before and after the transformation"
Fig.5
Relationship curve between the flow rate of the water feed pump group and the active power of the motor before and after the transformation"
Table 5
Power- and energy-saving of the unit under different operating conditions"