Shandong Science ›› 2022, Vol. 35 ›› Issue (3): 54-61.doi: 10.3976/j.issn.1002-4026.2022.03.007

• Energy and Power • Previous Articles     Next Articles

Energy-saving analysis of the frequency conversion transformation of an electric boiler water feed pump of the deep peak regulation unit

ZHAO Xue-shan(),PAN Xiao-jun*   

  1. Graduate School of Nanjing Institute of Technology, Nanjing 211167, China
  • Received:2021-05-18 Online:2022-06-20 Published:2022-06-10
  • Contact: Xiao-jun PAN E-mail:1040744362@qq.com

Abstract:

To improve the throttling loss of an electric water feed pump during the deep peak shaving operation of northeast coal-fired units, and the utilization rate of electric energy and coal consumption, a 600 MW electric water feed pump unit in power plant is taken as an example, using a frequency conversion scheme, under different working conditions (100%, 92%, 83%, 67%, 60%, 53%, and 50% rated loads), to analyze the power and frequency conversion conditions of single and double water feed pumps and identify the relationship between the flow rate, load, electrical efficiency, and active power of the motor. The test results show that the lower the flow, the more greater will be the improvements in the electrical efficiency and active power of the motor, up to 30% and 33%, respectively, subsequent to frequency conversion. Frequency conversion transformation is suitable for this unit, reducing the plant power consumption rate by 0.45%~0.87%, the power saving rate is 21%~33%. The variable frequency drive has a significant energy-saving effect on the deep peak shaving operation of the unit, providing a certain degree of reference for the transformation of the same type of unit.

Key words: :deep peak shaving, power plant boiler water feed pump, frequency conversion transformation, power saving, energy saving

CLC Number: 

  • TM343